Yokogawa EJA120A Draft Range Differential Pressure Transmitter

Ocean Part supply Yokogawa EJA120A Draft Range Differential Pressure Transmitter with best price for our clients. Full part number of  Yokogawa Draft Range pressure transmitter EJA120A series is EJA120A-EES4B-94EB/KU2/E1/M11/T04 and we can provide this part for industrial.

The EJA-A series is Yokogawa’s most successful pressure transmitter line. First released in 1991, it continues to offer high performance and high reliability for any application. With an installed base of over 4-1/2 million EJA-A transmitters worldwide, it has a proven track record that makes it a true industry workhorse.

The EJA120A is the traditional-mount Draft Range Pressure transmitter in the series.

 

Yokogawa EJA120A Differential Pressure Transmitter
Yokogawa EJA120A Differential Pressure Transmitter

 

 

Yokogawa EJA120A Differential Pressure Transmitter Information

The high performance Yokogawa draft range differential pressure transmitter model EJA120A outputs a 4 to 20 mA DC signal corresponding to the measured differential pressure. The Yokogawa EJA Series is available with BRAIN, HART, FOUNDATION™ fieldbus or PROFIBUS PA communication protocols.

Key EJA120A features include:

0.2% Accuracy (0.1% Accuracy available with /HAC option)
300 msec Response Time (with /F1 option)
True Draft Range design

Yokogawa Differential Pressure Transmitter EJA Series

– EJA110A Differential Pressure Transmitter

– EJA210A Draft Range Differential Pressure Transmitter

– EJA310A High Static Differential Pressure Transmitter

– EJA210/ EJA220A Flange Mounted Differential Pressure Transmitter

Specifications of Yokogawa EJA120A Draft Range Differential Pressure Transmitter

Yokogawa EJA120A Draft Range Differential Pressure Transmitter

E Capsule

Range

-1 to 1 kPa(-4 to 4 inH2O)

Span

0.1 to 1 kPa(0.4 to 4 inH2O)

Accuracy

±0.2%

Degrees of protection

IP67, NEMA 4X, and JIS C0920 immersion proof

Certificates

FM, CENELEC ATEX, CSA, IECEx

Output

4 to 20 mA DC or FOUNDATION™ fieldbus or PROFIBUS PA 2-wire system with digital communication

Supply voltage

BRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type)
Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity model and 9 to 17.5 V DC for FISCO model)

Ambient temperature

-25 to 80 deg C (-13 to 176 deg F)

Process temperature

-25 to 80 deg C (-13 to 176 deg F)

Maximum working pressure

50 kPa (7.25 psi)

Mounting

2-inch pipe mounting

Wetted parts material

Capsule

SUS316L(Diaphragm material is Hastelloy C-276)

Cover flange

SUS316

Housing

Cast aluminum

More Products  Yokogawa EJA110A Differential Pressure Transmitter

Download yokogawa pressure transmitter manual from here


Do you have inquiry? Ocean Part is a Powerful Yokogawa EJA120A Draft Range Differential Pressure Transmitter supplier. Please click to Send inquiry.


 

Leave a Reply